Product Info:
Main Features:
◆Output power range:500VA-180kVA;
◆Single phase AC output:115V,±20%adjustable;Three phase AC output:115V/200V(or 21/36V), ±20% adjustable;
◆Output frequency adjustable: (1)400Hz settled frequency output (2)320-480Hz alterable frequency;
◆Adopt ARM control, comes with serial communication interface, can connect with computer through remote communication control;
◆Adopt intelligent IGBT(IPM) output, excellent protection function;
◆Adopt SPWM technology, small size, light weight, and low noise;
◆120°phase lock, create up to three-phase output through single-phase product of phase locking;
◆Isolated transformer output for additional durability;
◆Supply pure and stable sine wave power, waveform distortion rate better than
2%,output voltage adjustable up to ±20%;
◆Fast output: steady within 2ms,100% load change, linear load steady is ±1% immediately;
◆Strong overload capacity, able to run continuously within 120% of its capacity. When operate at 150%, supply voltage will be disconnected in 600s, and 15s when operate at 200%
Standards:
◆International Standard Organization:ISO6858
◆USA Aviation Standard:MIL-STD-704E
◆China Aviation Standard:GJB572-88
◆China Civil Aviation Standard:MH/T6018-1999
Technical Parameters:
|
Model |
AN17001ST/36(F) |
|
Output Capacity |
1.5kVA |
|
Rated Output Current |
24A |
|
AC Input |
Input Voltage |
220V±22V / 380V ±40V |
|
Input Frequency |
50/60Hz±5Hz Single phase/3-phase 3-line |
|
AC Output |
Output Voltage |
①Rated Output Voltage:21V(phase)/36V(Line)
②Adjustable Output Voltage:16V-25V(phase)/28-43V(Line) |
|
Output Freq. |
①Rated Output Frequency:400Hz±0.4Hz
②Adjustable Output Frequency:320-480Hz |
|
Instantaneous
Characteristics |
Max overshoot Range ≤10%
Total Transient Recovery Time ≤20ms |
|
Wave distortion(THD) |
≤2% (Resistive load) |
|
Wave Peak Factor |
≤1.41±0.10 |
|
Harmonic Content |
≤1.5% |
|
Voltage Module Rate |
≤2.5V |
|
DC Content |
≤±0.1V |
|
Display (4-bit) |
Frequency |
(Highest)Resolution: 0.1Hz MAX Permitting Error: ±0.1% |
|
Voltage |
±1V |
|
Current |
(Highest)Resolution 0. 1A MAX Permitting Error: ±2.5% |
|
Efficiency |
≥85% |
|
Unbalanced Load on three phase |
MAX difference per phase ≤1.5V |
|
Phase Displacement |
120°±2°(在对称负载和额定电流的10%不平衡负载下) |
|
Preset Function |
Preset output voltage, output frequency, output voltage upper and lower percent |
|
Memory Function |
Memory voltage, frequency preset value |
|
Alarm Function |
Alarm signal after protection action |
|
Protection Function |
Input lack-phase protection, input short-circuit protection, over-heat protection, output lack-phase protection,
Remark:(Display corresponding code) |
|
Over Load Capacity |
With in 120% can continues run, when 125% 600s cut, when 150% 60s cut, when 200% 15s cut.
(Remark: Load of power factor is 0.8) |
|
Noise |
≤70dB(A) |
|
Display Mode |
LED |
|
Chassis Mode |
Stand-up |
|
Dimension W×H×D(mm) |
400×720×700 |
|
Case Protection Class |
Inner:IP2X;0℃-+40℃(Standard Series, Low Voltage Output Series) External: GJB 1440 Class 3 Category I -20℃~+50℃ (Mobile Trailer Mode) |
|
Accessories Optional |
①Aircraft Ground Connector(PJD-450HT or PJD-450HTB);
②Aviation Cable(10m,15m or 20m) |
|